Source author record

Xingpeng Li

Xingpeng Li appears in the imported research catalog. Authorship, coauthor and topic links are available while profile ownership is still unclaimed.

ResearcherUnclaimed source record

Catalog footprint

What is connected

21works
8topics
4close collaborators

Actions

Connect this record

Log in to claim

Research graph

See the researcher in context

Open full explorer

Inspect adjacent papers, topics, institutions and collaborators without losing the researcher page.

Building this map preview

BZPEER is loading the nearby papers, people, topics and institutions for this page.

Published work

21 published item(s)

preprint2023arXiv

Microgrid Optimal Energy Scheduling with Risk Analysis

Risk analysis is currently not quantified in microgrid resource scheduling optimization. This paper conducts a conditional value at risk (cVaR) analysis on a grid-disconnected residential microgrid with distributed energy resources (DER). We assume the infrastructure to set up an ad-hoc microgrid is already in place for a residential neighborhood with power sources such as photovoltaic (PV), diesel, and battery energy storage system (BESS). With this scenario in mind, we solve day-ahead scheduling to optimally allocate various resources to match demand in scenarios where neighborhoods, especially residential, are disconnected from the overall grid such as in flooding, hurricanes, winter storms, or operational failures. The goal is to provide an alternative framework to optimize power availability for priority customers and strengthen the overall grid against dips in power outside of normal operating considerations. The focus of this paper will be taking in renewable energy sources from PV combined with diesel and BESS while minimizing cost. Case studies demonstrate that with the proposed energy management system, microgrids can be implemented to be more resilient against new challenges.

preprint2022arXiv

A 100% Renewable Energy System: Enabling Zero CO2 Emission Offshore Platforms

The total electricity consumption from offshore oil/gas platforms is around 16 TWh worldwide in 2019. The majority offshore platforms are powered by the diesel generators while the rest mainly uses gas turbines, which emits large amounts of CO2 per year. The fast development of offshore wind turbines (WT) can potentially replace traditional fossil fuel based resources to power offshore loads. Thus, a novel offshore hybrid renewable energy sources (OHRES) system is proposed to enable a zero CO2 emission offshore platform mitigating climate change. Battery energy storage system (BESS) and hydrogen energy storage system (HESS) are considered to mitigate the fluctuation of wind power in the proposed OHRES system. Resilience models are designed to enhance the resilience of the proposed OHRES system with extra energy stored in BESS and/or HESS. Case studies demonstrate the feasibility of the proposed OHRES system to power offshore platforms. The economic analysis reports the planning cost for the proposed OHRES system under different resilience levels, which may benefit the decision to balance the carbon emission and investment cost.

preprint2022arXiv

An Alternative Method for Solving Security-Constrained Unit Commitment with Neural Network Based Battery Degradation Model

Battery energy storage system (BESS) can effectively mitigate the uncertainty of variable renewable generation and provide flexible ancillary services. However, degradation is a key concern for rechargeable batteries such as the most widely used Lithium-ion battery. A neural network based battery degradation (NNBD) model can accurately quantify the battery degradation. When incorporating the NNBD model into security-constrained unit commitment (SCUC), we can establish a battery degradation based SCUC (BD-SCUC) model that can consider the equivalent battery degradation cost precisely. However, the BD-SCUC may not be solved directly due to high non-linearity of the NNBD model. To address this issue, the NNBD model is linearized by converting the nonlinear activation function at each neuron into linear constraints, which enables BD-SCUC to become a linearized BD-SCUC (L-BD-SCUC) model. Case studies demonstrate the proposed L-BD-SCUC model can be efficiently solved for multiple BESS buses power system day-ahead scheduling problems with the lowest total cost including the equivalent degradation cost and normal operation cost.

preprint2022arXiv

Centralized Networked Micro Water-Energy Nexus with Proportional Exchange Among Participants

This paper proposes a Networked Micro Water-Energy Nexus (NetMicroWEN) capable of co-optimizing and simultaneously supplying water and energy to local consumers in nearby communities. The system manages different water and energy inputs of different communities in a local network to cooperatively meet their demands. This paper considers a centralized network topology that connects all members of the network under one control system. This paper also proposes a Proportional Exchange Algorithm (PEA) that allows members to benefit equally from exchanging both resources among other members of the NetMicroWEN and the main water and power distribution systems. The co-optimization model is a mixed-integer linear program, involving all necessary power and water related constraints for the network to achieve a feasible and practical solution. The economic benefits of the NetMicroWEN are illustrated by a comparison with separate Micro Water- Energy Nexus (MWEN) systems meeting their own demands individually. The case studies demonstrate that the proposed NetMicroWEN achieves substantially lower operating costs compared to the operation of separate MWEN systems.

preprint2022arXiv

Deep Learning based Security-Constrained Unit Commitment Considering Locational Frequency Stability in Low-Inertia Power Systems

With the goal of electricity system decarbonization, conventional synchronous generators are gradually replaced by converter-interfaced renewable generations. Such transition is causing concerns over system frequency and rate-of-change-of-frequency (RoCoF) security due to significant reduction in system inertia. Existing efforts are mostly derived from uniform system frequency response model which may fail to capture all characteristics of the systems. To ensure the locational frequency security, this paper presents a deep neural network (DNN) based RoCoF-constrained unit commitment (DNN-RCUC) model. RoCoF predictor is trained to predict the highest locational RoCoF based on a high-fidelity simulation dataset. Training samples are generated from models over various scenarios, which can avoid simulation divergence and system instability. The trained network is then reformulated into a set of mixed-integer linear constraints representing the locational RoCoF-limiting constraints in unit commitment. The proposed DNN-RCUC model is studied on the IEEE 24-bus system. Time domain simulation results on PSS/E demonstrate the effectiveness of the proposed algorithm.

preprint2022arXiv

Feasibility Layer Aided Machine Learning Approach for Day-Ahead Operations

Day-ahead operations involves a complex and computationally intensive optimization process to determine the generator commitment schedule and dispatch. The optimization process is a mixed-integer linear program (MILP) also known as security-constrained unit commitment (SCUC). Independent system operators (ISOs) run SCUC daily and require state-of-the-art algorithms to speed up the process. Existing patterns in historical information can be leveraged for model reduction of SCUC, which can provide significant time savings. In this paper, machine learning (ML) based classification approaches, namely logistic regression, neural networks, random forest and K-nearest neighbor, were studied for model reduction of SCUC. The ML was then aided with a feasibility layer (FL) and post-process technique to ensure high-quality solutions. The proposed approach is validated on several test systems namely, IEEE 24-Bus system, IEEE-73 Bus system, IEEE 118-Bus system, 500-Bus system, and Polish 2383-Bus system. Moreover, model reduction of a stochastic SCUC (SSCUC) was demonstrated utilizing a modified IEEE 24-Bus system with renewable generation. Simulation results demonstrate a high training accuracy to identify commitment schedule while FL and post-process ensure ML predictions do not lead to infeasible solutions with minimal loss in solution quality.

preprint2022arXiv

Generalized Dynamic Junction Theory to Resolve the Mechanism of Direct Current Generation in Liquid-Solid Interfaces

Despite the unsettled mechanism of electricity generation from the continuous flow of liquids on a surface, the charge-discharge theory has been widely accepted for alternating current (AC) generation from a moving droplet. It has been recently extended to rationalize direct current (DC) generation across a droplet moving between two different materials. By designing a reconfigurable contact between a metal wire and a water droplet moving on graphene, we show that the charge-discharge theory cannot explain the reversal of current when water-metal interfaces switch from dynamic to static. All experiments can be described after we distinguish a dynamic from a static interface and generalize the photovoltaic-like effect to all dynamic junctions: excited electrons and holes in a moving interface will be separated and swept under the built-in electrical field, leading to a DC response. This generalized theory will lead to an understanding and the design of efficient electricity generation based on interfacial charge transfer.

preprint2022arXiv

Machine Learning Assisted Approach for Security-Constrained Unit Commitment

Security-constrained unit commitment (SCUC) is solved for power system day-ahead generation scheduling, which is a large-scale mixed-integer linear programming problem and is very computationally intensive. Model reduction of SCUC may bring significant time savings. In this work, a novel approach is proposed to effectively utilize machine learning (ML) to reduce the problem size of SCUC. An ML model using logistic regression (LR) algorithm is proposed and trained with historical nodal demand profiles and the respective commitment schedules. The ML outputs are processed and analyzed to reduce variables and constraints in SCUC. The proposed approach is validated on several standard test systems including IEEE 24-bus system, IEEE 73-bus system, IEEE 118-bus system, synthetic South Carolina 500-bus system and Polish 2383-bus system. Simulation results demonstrate that the use of the prediction from the proposed LR model in SCUC model reduction can substantially reduce the computing time while maintaining solution quality.

preprint2022arXiv

Neural Network-based Power Flow Model

Power flow analysis is used to evaluate the flow of electricity in the power system network. Power flow calculation is used to determine the steady-state variables of the system, such as the voltage magnitude/phase angle of each bus and the active/reactive power flow on each branch. The DC power flow model is a popular linear power flow model that is widely used in the power industry. Although it is fast and robust, it may lead to inaccurate line flow results for some transmission lines. Since renewable energy sources such as solar farms or offshore wind farms are usually located far away from the main grid, accurate line flow results on these critical lines are essential for power flow analysis due to the unpredictable nature of renewable energy. Data-driven methods can be used to partially address these inaccuracies by taking advantage of historical grid profiles. In this paper, a neural network (NN) model is trained to predict power flow results using historical power system data. Although the training process may take time, once trained, it is very fast to estimate line flows. A comprehensive performance analysis between the proposed NN-based power flow model and the traditional DC power flow model is conducted. It can be concluded that the proposed NN-based power flow model can find solutions quickly and more accurately than DC power flow model.

preprint2022arXiv

Resilient Operational Planning for Microgrids Against Extreme Events

This paper proposes a novel resilience index, a microgrid survivability rate (SR) under extreme events, and then proposes a novel Resilient Operational Planning (ROP) algorithm to maximize the proposed resilience index SR. The proposed ROP algorithm can incorporate predetermined inverter failure probabilities and generate multiple scenarios accordingly to optimize resilient operations during an extreme event. The implemented ROP algorithm consists of two main steps: (i) optimization of resilient operational planning, and (ii) preventive resilience enhancement if minimum SR is not met per the analysis in step 1. A typical microgrid (MG) is studied to compare the proposed ROP algorithm against a traditional microgrid energy management (MEM) model. Results indicate that an enhanced resilience operation is achieved by the ROP algorithm, which is demonstrated by the quantification of resilience via the SR. Moreover, the proposed ROP algorithm is able to obtain a greater SR overall compared to that achieved by the traditional MEM, and this benefit of using the proposed ROP increases as the inverter failure probabilities increase.

preprint2022arXiv

Security-Constrained Unit Commitment Con-sidering Locational Frequency Stability in Low-Inertia Power Grids

With increasing installation of wind and solar generation, conventional synchronous generators in power systems are gradually displaced resulting in a significant reduction in system inertia. Maintaining system frequency within acceptable ranges becomes more critical for the stability of a power system. In this paper, we first study the impact of inter-area oscillations on the system rate-of-change-of-frequency (RoCoF) security; then, the limitations on locational RoCoFs accounting for G-1 contingency stability are derived. By enforcing these frequency related constraints, a location based RoCoF constrained security constrained unit commitment (LRC-SCUC) model is proposed. Furthermore, an effective piecewise linearization (PWL) technique is employed to formulate a RoCoF linearization problem and linearize the nonlinear function representing the location based RoCoF constraints in SCUC. Simulation results reveal that the inclusion of inertia-related constraints can substantially improve the system stability at the cost of higher operation cost. The results also show that deploying virtual inertia techniques not only reduces the total cost, but also improves the system market efficiency.

preprint2022arXiv

The Benefits of Hydrogen Energy Transmission and Conversion Systems to the Renewable Power Grids: Day-ahead Unit Commitment

The curtailment of renewable energy is more frequently observed as the renewable penetration levels are rising rapidly in modern power systems. It is a waste of free and green renewable energy and implies current power grids are unable to accommodate more renewable sources. One major reason is that higher power transmission capacity is required for higher renewable penetration level. Another major reason is the volatility of the renewable generation. The hydrogen mix or pure hydrogen pipeline can both transfer and store the energy in the form of hydrogen. However, its potential of accelerating renewable integration has not been investigated. In this paper, hydrogen pipeline networks, combined with power-to-hydrogen (P2H) and hydrogen-to-power (H2P) facilities, are organized to form a Hydrogen Energy Transmission and Conversion System (HETCS). We investigate the operation of power systems coupled with HETCS, and propose the day-ahead security-constrained unit commitment (SCUC) with HETCS. The SCUC simulation is conducted on a modified IEEE 24-bus power system with HETCS. Simulation results show HETCS can substantially reduce the renewable curtailment, CO2 emission, load payment and total operational cost. This study validates the HETCS can be a promising solution to achieve net-zero renewable grids.

preprint2020arXiv

A Novel Real-Time Energy Management Strategy for Gird-Friendly Microgrid: Harnessing Internal Fluctuation Internally

Typically, a large portion of microgrid generating capacity is from variable renewable resources that are greatly impacted by the environment and can be intermittent as well as stochastic. This would result in uncertainty of microgrid net-load, and negatively affect the grid reliability. A two-phase real-time energy management strategy for networked microgrid is proposed in this paper to address microgrid internal fluctuation internally, which enables a microgrid to become grid-friendly. The proposed strategy is based on coordination between the real-time dispatch (RTD) phase and the real-time control (RTC) phase. In the RTD phase, model predictive control (MPC) is used to optimally dispatch microgrid resources in the current time interval while considering near future situations. The RTC phase addresses microgrid internal net-load fluctuation with fast-acting batteries, which aims to maintain a constant tie-line power flow between the main grid and the microgrid for the current dispatch interval. Numerical simulations conducted on ten different net-load scenarios can demonstrate the performance of the proposed two-phase energy management strategy that will enable a microgrid to operate as a controllable asset with static electricity consumption or production in an economic dispatch interval from the perspective of the bulk grid operator.

preprint2020arXiv

An Accelerated-Decomposition Approach for Security-Constrained Unit Commitment with Corrective Network Reconfiguration- Part II: Results and Discussion

This paper presents a novel approach to handle the computational complexity in security-constrained unit commitment (SCUC) with corrective network reconfiguration (CNR) to harness the flexibility in transmission networks. This is achieved with consideration of scalability through decomposing the SCUC/SCUC-CNR formulation and then fast screening non-critical sub-problems. This is compared against the extensive formulations of SCUC and SCUC-CNR to show the advantages of the proposed typical-decomposition and accelerated-decomposition approaches to SCUC and SCUC-CNR respectively. Simulation results on the IEEE 24-bus system show that the proposed methods are substantially faster without the loss in solution quality. The proposed accelerated-decomposition approaches can be implemented for large power systems as they have great performance in the scalability tests on the IEEE 73-bus system and the Polish system when compared against the respective extensive formulations and typical-decomposition approaches. Overall, a dynamic post-contingency network can substantially alleviate network congestion and lead to a lower optimal cost.

preprint2020arXiv

Benefits and Cyber-Vulnerability of Demand Response System in Real-Time Grid Operations

With improvement in smart grids through two-way communication, demand response (DR) has gained significant attention due to the inherent flexibility provided by shifting non-critical loads from peak periods to off-peak periods, which can greatly improve grid reliability and reduce cost of energy. Operators utilize DR to enhance operational flexibility and alleviate network congestion. However, the intelligent two-way communication is susceptible to cyber-attacks. This paper studies the benefits of DR in security-constrained economic dispatch (SCED) and then the vulnerability of the system to line overloads when cyber-attack targets DR signals. This paper proposes a false demand response signal and load measurement injection (FSMI) cyber-attack model that sends erroneous DR signals while hacking measurements to make the attack undetectable. Simulation results on the IEEE 24-bus system (i) demonstrate the cost-saving benefits of demand response, and (ii) show significant line overloads when the demand response signals are altered under an FSMI attack.

preprint2020arXiv

Dynamic Estimation of Power System Inertia Distribution Using Synchrophasor Measurements

Integration of intermittent renewable energy sources in modern power systems is increasing very fast. Replacement of synchronous generators with zero-to-low variable renewables substantially decreases the system inertia. In a large system, inertia distribution may vary significantly, areas of low inertia are more susceptible to frequency deviation, posing risks of load shedding and generation trip. Therefore, it is necessary for operators to evaluate and quantify the system inertia and its distribution in real time. This paper proposes a novel synchronized phasor measurement units (PMUs)-based dynamic system inertia estimation method. The proposed inertia estimation method is derived using electrical distance and clustering algorithm, which considers the impact of location of measurements relative to in-feed load and impact of oscillations. The center of inertia (COI) area and area of low inertia are also determined during the estimation. Numerical simulations are conducted on the IEEE 24-bus system with various load profiles using Transient Security Analysis Tools (TSAT), a core module of the DSATools, which demonstrate the efficacy of the proposed approach.

preprint2020arXiv

Enhancing System Flexibility through Corrective Demand Response in Security-Constrained Unit Commitment

Currently, system operators implement demand response by dispatching controllable loads for economic reasons in day-ahead scheduling. Particularly, demand shifting from peak hours when the cost of electricity is higher to non-peak hours to maintain system reliability by flattening the load profile. However, the system flexibility and economic benefits of such action in post-contingency scenarios are not explicitly considered in short-term operations. Hence, this paper highlights the benefits of demand response as a corrective action for potential post-contingency emergencies in day-ahead scheduling. A security-constrained unit commitment (SCUC) model which considers the flexibility offered through corrective demand response (CDR) to maintain system reliability when a line or generator outage occurs is proposed. The proposed model was tested on IEEE 24-bus system where simulation results point to significant total cost savings in daily operations. Moreover, the results point to better long-term reliability of generators along with the ability to use existing system flexibility and serve higher critical demands in base-case when CDR is implemented.

preprint2020arXiv

Reducing Congestion-Induced Renewable Curtailment with Corrective Network Reconfiguration in Day-Ahead Scheduling

Renewable energy sources (RES) has gained a lot of interest recently. The limited transmission capacity serving RES often leads to network congestion since they are located in remote favorable locations. As a result, when poorly scheduled, the intermittent nature of RES may result in high curtailments of the free resource. Currently, grid operators utilize a static network when performing day-ahead scheduling and ignore transmission flexibility. This paper explores the possibility of utilizing network reconfiguration as a corrective action to reduce the transmission congestion and thereby the reduction of RES curtailments in day-ahead scheduling. To facilitate the RES integration in the grid, a stochastic N-1 security-constrained unit-commitment with corrective network reconfiguration (SSCUC-CNR) is modelled. SSCUC-CNR model is studied on a modified IEEE 24-bus system with RES. The simulation results demonstrate that CNR not only leads to a lower cost solution by reducing network congestion but also facilitates RES integration by reducing congestion-induced curtailments in high penetration cases. Emission studies demonstrate that more green generators are committed resulting in reduced carbon emissions when CNR is implemented.

preprint2020arXiv

Security Constrained Unit Commitment with Corrective Transmission Switching

Traditionally, power system operations use a static network to deliver power and meet demand optimally. Network topology reconfiguration through transmission switching (TS) has gained significant interest recently to reduce the operational cost of power system operations. However, implementation of TS also causes large disturbance in the network and as a result the use of corrective transmission switching (CTS) in response to power system contingencies is currently being researched extensively. This paper emphasizes the importance of CTS to accomplish flexible transmission in N-1 security-constrained unit commitment (SCUC) model. An N-1 SCUC mathematical model implementing a dynamic network in the post-contingency scenario is proposed as opposed to current industry practices of static network in short-term operations. The proposed model is tested and validated on the IEEE 24-bus system. The proposed model results in cost-effective implementation and leads to overall reduced cost, and congestion reduction in the post-contingency scenario.

preprint2016arXiv

Real-Time Contingency Analysis with Corrective Transmission Switching - Part I: Methodology

Transmission switching (TS) has gained significant attention recently. However, barriers still remain and must be overcome before the technology can be adopted by the industry. The state of the art challenges include AC feasibility and performance, computational complexity, the ability to handle large-scale real power systems, and dynamic stability. This two-part paper investigates these challenges by developing an AC TS-based real-time contingency analysis (RTCA) tool that can handle large-scale systems within a reasonable time. The tool proposes multiple corrective switching actions, after detection of a contingency with potential violations. To reduce the computational complexity, three heuristic algorithms are proposed to generate a small set of candidates for switching. Parallel computing is implemented to further speed up the solution time. Furthermore, stability analysis is performed to check for dynamic stability of proposed TS solutions. Part I of the paper presents a comprehensive literature review and the methodology. The promising results, tested on the Tennessee Valley Authority (TVA) system and actual energy management system (EMS) snapshots from Pennsylvania New Jersey Maryland (PJM) and the Electric Reliability Council of Texas (ERCOT), are presented in Part II. It is concluded that RTCA with corrective TS significantly reduces potential post-contingency violations and is ripe for industry adoption.

preprint2016arXiv

Real-Time Contingency Analysis with Corrective Transmission Switching - Part II: Results and Discussion

This paper presents the performance of an AC transmission switching (TS) based real-time contingency analysis (RTCA) tool that is introduced in Part I of this paper. The approach quickly proposes high quality corrective switching actions for relief of potential post-contingency network violations. The approach is confirmed by testing it on actual EMS snapshots of two large-scale systems, the Electric Reliability Council of Texas (ERCOT) and the Pennsylvania New Jersey Maryland (PJM) Interconnection; the approach is also tested on data provided by the Tennessee Valley Authority (TVA). The results show that the tool effectively reduces post-contingency violations. Fast heuristics are used along with parallel computing to reduce the computational difficulty of the problem. The tool is able to handle the PJM system in about five minutes with a standard desktop computer. Time-domain simulations are performed to check system stability with corrective transmission switching (CTS). In conclusion, the paper shows that corrective switching is ripe for industry adoption. CTS can provide significant reliability benefits that can be translated into significant cost savings.