Abstract
The area angle is a scalar measure of power system area stress that responds to line outages within the area and is a combination of synchrophasor measurements of voltage angles around the border of the area. Both idealized and practical examples are given to show that the variation of the area angle for single line outages can be approximately related to changes in the overall susceptance of the area and the line outage severity.