Abstract
We develop a consistent model for a Line Lightning Protection Device and demonstrate that this model can explain the two modes of current quenching -- impulse quenching and current zero quenching -- observed in such devices. A dimensional analysis shows that impulse quenching can always be obtained if the power loss from the electric arcs is large enough as compared to , where is the grid voltage and is the maximum follow current after a lightning strike. We further show that the two modes of quenching can be reproduced in a full 3D arc simulations coupled to the appropriate circuit model. This means the arc simulations can be used for optimization and development of future LLPDs.
Connections
Explore this paper’s authors, topics and related work.
Building this map preview
BZPEER is loading the nearby papers, people, topics and institutions for this page.
Reviews 0
Write a review
No reviews yet.
Discussion 0
Add a comment
No comments yet.